DPS Series 300-1200 kVA

The Next Generation UPS Answering the Demand of Large Data Centers and Colocations

Delta's superior Ultron DPS series 300-1200 kVA UPS supports unity output power factor to deliver up to 10 MW power capacity to meet the demands for large data centers and colocations that require higher power capacity. The Ultron DPS series guarantees the highest level of system reliability and resiliency by supporting self-detection of key components with pre-warning function, multilayered redundancy design, and complete power rating coverage. Moreover, the DPS series supports advanced manageability. Key environment parameters, and event analysis can all be monitored via local 10" LCD monitor and remotely. Along with optional battery management software, the DPS series enables users to achieve predictive maintenance and minimize system downtime, while lowering the total cost of ownership (TCO).

Fully front access and modular design of key components simplifies maintenance and shorten the mean time to repair (MTTR)
Downloads Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Ultimate Availability

  • Supports up to 10 MW power capacity with the parallel redundancy and expansion up to 8 units
  • Redundancy components and dual CAN bus ensures system availability
  • Proactive detection of key component status for early diagnosis on UPS malfunction
  • Intelligent battery health diagnosis enables better battery maintenance and replacement
  • Advanced event analysis, including 10,000 event logs, waveform capturing and key paremeters recording, to detect UPS abnomality and ensure higher availability
 

Excellent Performance

  • The industry's leading power density and smallest footprint with the design of both top/bottom cable entry* and inbuilt switches
    (* For DPS-300K, only top cable entry is available)
  • Unity output power factor guarantees no-rating and provides 100% kW
  • AC-AC efficiency of up to 96.5% and 99% in ECO mode resulting in marked energy cost savings
  • Supports both VRLA and environment-friendly Li-ion batteries
 

Sophisticated Manageability and Flexibility

  • User-friendly 10” color touch panel simplifies local UPS management
  • Environment information, such as security, water, fire, and temperature can be integrated and monitored via the LCD panel of the UPS
  • If the UPS is equipped with an external battery management system, the battery information can be integrated and monitored via the LCD panel of the UPS
  • Fully front access and modular design of key components shortens the mean time to repair (MTTR)
  • Flexible battery quantity of 30-46 pcs achieves optimal battery investment
Applications

UPS DPS Series applications

Specifications
  1. Model
  2. DPS-300K: Power Rating - 300kVA / 300kW
    DPS-400K: Power Rating - 400kVA / 400kW
    DPS-500K: Power Rating - 500kVA / 500kW
    DPS-600K: Power Rating - 600kVA / 600kW
    DPS-800K: Power Rating - 800kVA / 800kW
    DPS-1000K: Power Rating - 1000kVA / 1000kW
    DPS-1200K: Power Rating - 1200kVA / 1200kW

  3. Input
  4. Nominal Voltage: 220/380Vac, 230/400Vac, 240/415Vac (3-phase, 4-wire + G)
  5. Voltage Range: 176/304~276/478Vac (full load)
  6. Current Harmonic Distortion: < 3% (with Full Linear Load); < 5% (with Full Non-linear Load)
  7. Power Factor: > 0.99
  8. Frequency Range: 40~70Hz

  9. Output
  10. Voltage: 220/380Vac, 230/400Vac, 240/415Vac (3-phase, 4-wire + G)
  11. Voltage Harmonic Distortion: < 1.5% (Linear Load); < 5% (Non-linear Load)
  12. Voltage Regulation: ±1 (static); ±5 (dynamic)
  13. Output Power Factor: 1
  14. Frequency: 50/60Hz (Auto-Selectable)
  15. Overload Capability: ≤ 125%: 10min; ≤ 150%: 1min; > 150%: 1sec

  16. Display : 10” Color Touch Panel

  17. Interface
  18. Standard: RS232, Parallel port, USB, Modbus RS485, Input dry contact, Output dry contact, SNMP card inbuilt in touch screen
  19. Optional: Relay I/O card, Battery cabinet temperature sensor cable

  20. Conformance
  21. Safety: CE

  22. Efficiency
  23. AC-AC: Up to 96.5%
  24. ECO Mode: 99%

  25. Battery
  26. Type: VRLA, LiB
  27. Charge Current
    DPS-300K: 90A
    DPS-400K: 120A
    DPS-500K: 150A
    DPS-600K: 180A
    DPS-800K: 240A
    DPS-1000K: 300A
    DPS-1200K: 360A
  28. Battery Quantity: 30~46pcs

  29. Environment
  30. Operating Temperature: 0~40℃
  31. Relative Humidity: 0~95% (non-condensing)
  32. Audible Noise: < 80dB
  33. IP Protection: IP 20

  34. Others
  35. Parallel Redundancy and Expansion: Maximum 8 units
  36. Emergency Power Off: Remote and local

  37. Physical
  38. Dimensions (W x D x H)
    DPS-300K: 600* x 900 x 2000mm
    DPS-400K/500K/600K: 1200* x 900 x 2000mm
    DPS-800K: 1800 x 900 x 2000mm
    DPS-1000K/1200K: 2450 x 900 x 2000mm
  39. Weight
    DPS-300K: 515kg
    DPS-400K: 700kg
    DPS-500K: 811kg
    DPS-600K: 970kg
    DPS-800K: 1270kg
    DPS-1000K: 1850kg
    DPS-1200K: 2000kg

  40. * The width is for the cabinet which has four inbuilt switches.